Vapor barrier
Insulation & moisture · Calculator

Vapor barrier calculator

Rolls of 6-mil poly for a wall or ceiling. The overlap is counted as linear seams, not a flat percentage, and the climate-zone check that decides whether the sheet belongs on the inside at all is built in.

A
Detail A — Poly roll count
Area to cover—
Courses across span—
Pieces along run—
Field seams to tape—
Material (with waste)—
— Rolls to order
—

01 How the math works

Start with the surface area: run × height for a wall, length × width for a ceiling or floor. Then decide how the roll lands on it. Vapor-barrier poly comes in wide rolls — commonly 10 ft (3.05 m) or 20 ft (6.10 m) face width by 100 ft (30.48 m) long. The face width is almost always enough to span a standard wall height in one pass.

Area = A × B
Courses across the span = ⌈(span − lap) ÷ (roll width − lap)⌉
Pieces along the run = ⌈(run − lap) ÷ (roll length − lap)⌉
Rolls = ⌈material area × (1 + waste) ÷ roll area⌉

The part most calculators get wrong is the overlap. A seam lap is a linear loss — it only happens where two sheets meet. Run a 10 ft roll along an 8 ft wall and the face width covers the full height in a single course, so there are no horizontal field seams: the only waste is the 2 ft of roll width you trim or lap at the floor. Treating that as a flat percentage is where the area-times-1.10 approach drifts. We count the courses and the laps, then round up to whole rolls.

02 Worked example

Take a cold-climate basement wall where the interior vapor retarder is required: a run of 40 ft × 8 ft high (12.19 m × 2.44 m), which is 320 ft² (29.73 m²). Cover it with a 10 ft × 100 ft (3.05 m × 30.48 m) roll of 6-mil poly and a 6 in (152 mm) lap.

Run the roll horizontally. The 10 ft face width spans the 8 ft height in one course — no horizontal seam — and the 40 ft run is under the 100 ft roll length, so no end-lap either. Material off the roll is 10 ft × 40 ft = 400 ft² (37.16 m²) to cover 320 ft² of wall. The 80 ft² (7.43 m²) difference is roll-width-versus-wall-height trim — 20% here, not the 10% a flat factor assumes.

One 10 ft × 100 ft roll holds 1,000 ft² (92.90 m²), so a single roll covers this wall and two more like it. Order one roll; the leftover is the handling margin.

03 When this calculator is wrong

The roll count is only half the question. The other half is whether a polyethylene sheet belongs on that surface at all, and here the honest answer depends on where the building is.

04 What to do with the result

Round up to whole rolls — poly is cheap and a short sheet means an untaped seam or a pieced-in patch where you least want one. The standard 10% cut-and-handling allowance holds for a straightforward wall or ceiling. For a small, cut-up job — a short run broken by windows, or a ceiling with a lot of fixtures — bump it to 15%, because small sheets have more edge waste and less margin to work with. The exception is a large, open, rectangular surface: there 10% is generous and you can trust the lower number.

Lap every seam 6 in (152 mm) over a framing member and seal it — an unsealed lap is a hole in the barrier, not a barrier. Confirm your climate zone against the zone check above before you buy: if it reads "not permitted," the roll count is moot and the money is better spent on air-sealing and a vapor-open finish.

05 Common questions

Which side of the wall does the vapor barrier go on?
The warm-in-winter side. In cold climates (IRC Zones 5, 6, 7, 8, and Marine 4) that's the interior face of the framing, under the drywall — which is where R702.7 requires it. Putting it on the cold side in those zones, or on the interior in a hot-humid climate, is how walls get wet.
Do I need a plastic vapor barrier in a hot climate?
Not on the interior of a frame wall. In Zones 1 through 3 an interior Class I poly sheet is not permitted — it traps moisture the humid outdoor air drives inward. Those walls use a vapor-open interior finish and rely on air-sealing instead. Poly is still correct under slabs and over crawlspace soil in any zone.
How much should vapor barrier overlap at the seams?
6 in (152 mm) is the common minimum — the figure ASTM E1643 sets for under-slab joints and the one most installers use on walls and ceilings too. Lap over a stud or joist and seal the seam with tape or sealant.
What thickness of poly is a vapor barrier?
6-mil (0.15 mm) polyethylene is the common construction grade for walls, ceilings, and crawlspaces. It tests well inside the IRC Class I range (0.1 perm or less). Under a slab, step up to a 10-mil-plus ASTM E1745 Class A product — thicker for puncture resistance and a tighter perm rating.
How many square feet are in a roll of vapor barrier?
Depends on the roll. A 10 ft × 100 ft roll is 1,000 ft² (92.90 m²); a 20 ft × 100 ft roll is 2,000 ft² (185.81 m²). That's the face area, before you subtract the overlap and trim — which is what the calculator above does.